DEHNventil modular
Résultat : 18/18 Produits
Le produit 956305 a été ajouté au bloc-notes
Le produit 956305 a été ajouté au panier.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Energy coordination with terminal equipment (≤ 10 m) | Type 1 + Type 2 + Type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal ) | 75 kA |
Lightning impulse current (10/350 µs) [L-PEN] (Iimp ) | 25 kA |
Specific energy [L-PEN] (W/R) | 156.25 kJ/ohms |
Nominal discharge current (8/20 µs) [L-PEN] (In ) | 25 kA |
Voltage protection level (UP ) | ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 6 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 50 kArms |
Follow current limitation / Selectivity | No tripping of a 35 A gG fuse up to 50 kArms (prosp.) |
Short-circuit current rating [L-N]/[N-PE] (ISCCR ) | 50 kArms |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 250 A gG |
Temporary overvoltage (TOV) (UT) – Characteristic | 440 V / 120 min. – withstand |
Let-through energy with an S20K275 (Iimp = 2.5 to 25 kA) | < 1 J |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L2, L3, PEN, 9) (min.) | 6 mm2 solid / fine-stranded |
Cross-sectional area (L1, L2, L3, PEN, 9) (max.) | 35 mm2 stranded / 25 mm2 fine-stranded |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | VDE, KEMA, UL |
Type of remote signalling contact | yes / changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / fine-stranded |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 250 A gG |
Use for 16.7 Hz traction power supply systems | |
– Test voltage AC (UC ) | 266 V |
– Nominal voltage (a.c.) (UN ) | 230 / 400 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 160 A gG @ 16,7 Hz |
Le produit 956405 a été ajouté au bloc-notes
Le produit 956405 a été ajouté au panier.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Energy coordination with terminal equipment (≤ 10 m) | Type 1 + Type 2 + Type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 100 kA |
Specific energy [L1+L2+L3+N-PE] (W/R) | 2.50 MJ/ohms |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 25 kA |
Specific energy [L,N-PE] (W/R) | 156.25 kJ/ohms |
Nominal discharge current (8/20 µs) [L/N-PE]/[L1+L2+L3+N-PE] (In ) | 25 / 100 kA |
Voltage protection level [L-PE]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 6 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 50 kArms |
Follow current limitation / Selectivity | No tripping of a 35 A gG fuse up to 50 kArms (prosp.) |
Short-circuit current rating [L-N]/[N-PE] (ISCCR ) | 50 kArms |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 250 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Let-through energy with an S20K275 (Iimp = 2.5 to 25 kA) | < 1 J |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L2, L3, N, PE, 9) (min.) | 6 mm2 solid / fine-stranded |
Cross-sectional area (L1, L2, L3, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 fine-stranded |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | VDE, KEMA, UL |
Type of remote signalling contact | yes / changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / fine-stranded |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 250 A gG |
Use for 16.7 Hz traction power supply systems | |
– Test voltage AC (UC ) | 266 V |
– Nominal voltage (a.c.) (UN ) | 230 / 400 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 160 A gG @ 16,7 Hz |
Le produit 956315 a été ajouté au bloc-notes
Le produit 956315 a été ajouté au panier.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Energy coordination with terminal equipment (≤ 10 m) | Type 1 + Type 2 + Type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) [L-N] (UC ) | 255 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) [N-PE] (UC (N-PE) ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 100 kA |
Specific energy [L1+L2+L3+N-PE] (W/R) | 2.50 MJ/ohms |
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) | 25 / 100 kA |
Specific energy [L-N]/[N-PE] (W/R) | 156.25 kJ/ohms / 2.50 MJ/ohms |
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In ) | 25 / 100 kA |
Voltage protection level [L-N]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 6 kV |
Follow current extinguishing capability [L-N]/[N-PE] (Ifi ) | 50 kArms / 100 Arms |
Follow current limitation / Selectivity | No tripping of a 35 A gG fuse up to 50 kArms (prosp.) |
Short-circuit current rating [L-N]/[N-PE] (ISCCR ) | 50 kArms / 100 Arms |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 250 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic | 1200 V / 200 ms – withstand |
Let-through energy with an S20K275 (Iimp = 2.5 to 25 kA) | < 1 J |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L2, L3, N, PE, 9) (min.) | 6 mm2 solid / fine-stranded |
Cross-sectional area (L1, L2, L3, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 fine-stranded |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Place of installation / Degree of protection | indoors / IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | VDE, KEMA, UL |
Type of remote signalling contact | yes / changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 250 A gG |
Supplementary data: | --------------------------------- |
– Voltage protection level [L-PE] (UP ) | 1.8 kV |
Use for 16.7 Hz traction power supply systems | |
– Test voltage AC (UC ) | 266 V |
– Nominal voltage (a.c.) (UN ) | 230 / 400 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 160 A gG @ 16,7 Hz |
Le produit 956205 a été ajouté au bloc-notes
Le produit 956205 a été ajouté au panier.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Energy coordination with terminal equipment (≤ 10 m) | Type 1 + Type 2 + Type 3 |
Nominal voltage (a.c.) (UN ) | 230 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) | 50 kA |
Specific energy [L+N-PE] (W/R) | 625.00 kJ/ohms |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 25 kA |
Specific energy [L,N-PE] (W/R) | 156.25 kJ/ohms |
Nominal discharge current (8/20 µs) [L/N-PE]/[L+N-PE] (In ) | 25 / 50 kA |
Voltage protection level [L-PE]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 6 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 50 kArms |
Follow current limitation / Selectivity | No tripping of a 35 A gG fuse up to 50 kArms (prosp.) |
Short-circuit current rating [L-N]/[N-PE] (ISCCR ) | 50 kArms |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 250 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Let-through energy with an S20K275 (Iimp = 2.5 to 25 kA) | < 1 J |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L, N, PE, 9) (min.) | 6 mm2 solid / fine-stranded |
Cross-sectional area (L, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 fine-stranded |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 2 module(s), DIN 43880 |
Approvals | VDE, KEMA, UL |
Type of remote signalling contact | yes / changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / fine-stranded |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 250 A gG |
Use for 16.7 Hz traction power supply systems | |
– Test voltage AC (UC ) | 266 V |
– Nominal voltage (a.c.) (UN ) | 230 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 160 A gG @ 16,7 Hz |
Le produit 956115 a été ajouté au bloc-notes
Le produit 956115 a été ajouté au panier.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Energy coordination with terminal equipment (≤ 10 m) | Type 1 + Type 2 + Type 3 |
Nominal voltage (a.c.) (UN ) | 230 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) [L-N] (UC ) | 255 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) [N-PE] (UC (N-PE) ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) | 50 kA |
Specific energy [L+N-PE] (W/R) | 625.00 kJ/ohms |
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) | 25 / 50 kA |
Specific energy [L-N]/[N-PE] (W/R) | 156.25 / 625.00 kJ/ohms |
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In ) | 25 / 50 kA |
Voltage protection level [L-N]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 6 kV |
Follow current extinguishing capability [L-N]/[N-PE] (Ifi ) | 50 kArms / 100 Arms |
Follow current limitation / Selectivity | No tripping of a 35 A gG fuse up to 50 kArms (prosp.) |
Short-circuit current rating [L-N]/[N-PE] (ISCCR ) | 50 kArms / 100 Arms |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 250 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic | 1200 V / 200 ms – withstand |
Let-through energy with an S20K275 (Iimp = 2.5 to 25 kA) | < 1 J |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L, N, PE, 9) (min.) | 6 mm2 solid / fine-stranded |
Cross-sectional area (L, N, PE, 9) (max.) | 35 mm2 stranded / 25 mm2 fine-stranded |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Place of installation / Degree of protection | indoors / IP 20 |
Capacity | 2 module(s), DIN 43880 |
Approvals | VDE, KEMA, UL |
Type of remote signalling contact | yes / changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / fine-stranded |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 250 A gG |
Supplementary data: | --------------------------------- |
– Voltage protection level [L-PE] (UP ) | 1.8 kV |
Use for 16.7 Hz traction power supply systems | |
– Test voltage AC (UC ) | 266 V |
– Nominal voltage (a.c.) (UN ) | 230 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 160 A gG @ 16,7 Hz |
Le produit 951300 a été ajouté au bloc-notes
Le produit 951300 a été ajouté au panier.
Use for 16.7 Hz traction power supply systems | |
– Nominal voltage (a.c.) (UN ) | 230 / 400 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 125 A gG @ 16,7 Hz |
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 264 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal ) | 75 kA |
Specific energy [L1+L2+L3-PEN] (W/R) | 1.40 MJ/ohms |
Lightning impulse current (10/350 µs) [L-PEN] (Iimp ) | 25 kA |
Specific energy [L-PEN] (W/R) | 156.25 kJ/ohms |
Nominal discharge current (8/20 µs) [L-PEN]/[L1+L2+L3-PEN] (In ) | 25 / 75 kA |
Voltage protection level (UP ) | ≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 50 kArms |
Follow current limitation / Selectivity | no tripping of a 20 A gG fuse up to 50 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 315 A gG |
Max. backup fuse (L-L') | 125 A gG |
Temporary overvoltage (TOV) (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L1', L2, L2', L3, L3', PEN, 9) (min.) | 10 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, PEN) (max.) | 50 mm2 stranded / 35 mm2 flexible |
Cross-sectional area (L1', L2', L3', 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 6 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 315 A gG |
Le produit 951305 a été ajouté au bloc-notes
Le produit 951305 a été ajouté au panier.
Use for 16.7 Hz traction power supply systems | |
– Nominal voltage (a.c.) (UN ) | 230 / 400 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 125 A gG @ 16,7 Hz |
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 264 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal ) | 75 kA |
Specific energy [L1+L2+L3-PEN] (W/R) | 1.40 MJ/ohms |
Lightning impulse current (10/350 µs) [L-PEN] (Iimp ) | 25 kA |
Specific energy [L-PEN] (W/R) | 156.25 kJ/ohms |
Nominal discharge current (8/20 µs) [L-PEN]/[L1+L2+L3-PEN] (In ) | 25 / 75 kA |
Voltage protection level (UP ) | ≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 50 kArms |
Follow current limitation / Selectivity | no tripping of a 20 A gG fuse up to 50 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 315 A gG |
Max. backup fuse (L-L') | 125 A gG |
Temporary overvoltage (TOV) (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L1', L2, L2', L3, L3', PEN, 9) (min.) | 10 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, PEN) (max.) | 50 mm2 stranded / 35 mm2 flexible |
Cross-sectional area (L1', L2', L3', 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 6 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 315 A gG |
Le produit 951400 a été ajouté au bloc-notes
Le produit 951400 a été ajouté au panier.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 264 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 100 kA |
Specific energy [L1+L2+L3+N-PE] (W/R) | 2.50 MJ/ohms |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 25 kA |
Specific energy [L,N-PE] (W/R) | 156.25 kJ/ohms |
Nominal discharge current (8/20 µs) [L/N-PE]/[L1+L2+L3+N-PE] (In ) | 25 / 100 kA |
Voltage protection level [L-PE]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 50 kArms |
Follow current limitation / Selectivity | no tripping of a 20 A gG fuse up to 50 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 315 A gG |
Max. backup fuse (L-L') | 125 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L1', L2, L2', L3, L3', N, N', PE, 9) (min.) | 10 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, N, PE) (max.) | 50 mm2 stranded / 35 mm2 flexible |
Cross-sectional area (L1', L2', L3', N', 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 8 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 315 A gG |
Use for 16.7 Hz traction power supply systems | |
– Nominal voltage (a.c.) (UN ) | 230 / 400 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 125 A gG @ 16,7 Hz |
Le produit 951405 a été ajouté au bloc-notes
Le produit 951405 a été ajouté au panier.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 264 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 100 kA |
Specific energy [L1+L2+L3+N-PE] (W/R) | 2.50 MJ/ohms |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 25 kA |
Specific energy [L,N-PE] (W/R) | 156.25 kJ/ohms |
Nominal discharge current (8/20 µs) [L/N-PE]/[L1+L2+L3+N-PE] (In ) | 25 / 100 kA |
Voltage protection level [L-PE]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 50 kArms |
Follow current limitation / Selectivity | no tripping of a 20 A gG fuse up to 50 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 315 A gG |
Max. backup fuse (L-L') | 125 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L1', L2, L2', L3, L3', N, N', PE, 9) (min.) | 10 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, N, PE) (max.) | 50 mm2 stranded / 35 mm2 flexible |
Cross-sectional area (L1', L2', L3', N', 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 8 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 315 A gG |
Use for 16.7 Hz traction power supply systems | |
– Nominal voltage (a.c.) (UN ) | 230 / 400 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 125 A gG @ 16,7 Hz |
Le produit 951310 a été ajouté au bloc-notes
Le produit 951310 a été ajouté au panier.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) [L-N] (UC ) | 264 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) [N-PE] (UC (N-PE) ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 100 kA |
Specific energy [L1+L2+L3+N-PE] (W/R) | 2.50 MJ/ohms |
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) | 25 / 100 kA |
Specific energy [L-N]/[N-PE] (W/R) | 156.25 kJ/ohms / 2.50 MJ/ohms |
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In ) | 25 / 100 kA |
Voltage protection level [L-N]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability [L-N]/[N-PE] (Ifi ) | 50 kArms / 100 Arms |
Follow current limitation / Selectivity | no tripping of a 20 A gG fuse up to 50 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 315 A gG |
Max. backup fuse (L-L') | 125 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic | 1200 V / 200 ms – withstand |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L1', L2, L2', L3, L3', N, N', PE, 9) (min.) | 10 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, N, PE) (max.) | 50 mm2 stranded / 35 mm2 flexible |
Cross-sectional area (L1', L2', L3', N', 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 8 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 315 A gG |
Supplementary data: | --------------------------------- |
– Voltage protection level [L-PE] (UP ) | 2.2 kV |
Use for 16.7 Hz traction power supply systems | |
– Nominal voltage (a.c.) (UN ) | 230 / 400 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 125 A gG @ 16,7 Hz |
Le produit 951315 a été ajouté au bloc-notes
Le produit 951315 a été ajouté au panier.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) [L-N] (UC ) | 264 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) [N-PE] (UC (N-PE) ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 100 kA |
Specific energy [L1+L2+L3+N-PE] (W/R) | 2.50 MJ/ohms |
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) | 25 / 100 kA |
Specific energy [L-N]/[N-PE] (W/R) | 156.25 kJ/ohms / 2.50 MJ/ohms |
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In ) | 25 / 100 kA |
Voltage protection level [L-N]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability [L-N]/[N-PE] (Ifi ) | 50 kArms / 100 Arms |
Follow current limitation / Selectivity | no tripping of a 20 A gG fuse up to 50 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 315 A gG |
Max. backup fuse (L-L') | 125 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic | 1200 V / 200 ms – withstand |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L1, L1', L2, L2', L3, L3', N, N', PE, 9) (min.) | 10 mm2 solid / flexible |
Cross-sectional area (L1, L2, L3, N, PE) (max.) | 50 mm2 stranded / 35 mm2 flexible |
Cross-sectional area (L1', L2', L3', N', 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation / Degree of protection | indoors / IP 20 |
Capacity | 8 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 315 A gG |
Supplementary data: | --------------------------------- |
– Voltage protection level [L-PE] (UP ) | 2.2 kV |
Use for 16.7 Hz traction power supply systems | |
– Nominal voltage (a.c.) (UN ) | 230 / 400 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 125 A gG @ 16,7 Hz |
Le produit 951200 a été ajouté au bloc-notes
Le produit 951200 a été ajouté au panier.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 264 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) | 50 kA |
Specific energy [L+N-PE] (W/R) | 625.00 kJ/ohms |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 25 kA |
Specific energy [L,N-PE] (W/R) | 156.25 kJ/ohms |
Nominal discharge current (8/20 µs) [L/N-PE]/[L+N-PE] (In ) | 25 / 50 kA |
Voltage protection level [L-PE]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 50 kArms |
Follow current limitation / Selectivity | no tripping of a 20 A gG fuse up to 50 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 315 A gG |
Max. backup fuse (L-L') | 125 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L, L', N, N', PE, 9) (min.) | 10 mm2 solid / flexible |
Cross-sectional area (L, N, PE) (max.) | 50 mm2 stranded / 35 mm2 flexible |
Cross-sectional area (L', N', 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 315 A gG |
Use for 16.7 Hz traction power supply systems | |
– Nominal voltage (a.c.) (UN ) | 230 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 125 A gG @ 16,7 Hz |
Le produit 951205 a été ajouté au bloc-notes
Le produit 951205 a été ajouté au panier.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 264 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) | 50 kA |
Specific energy [L+N-PE] (W/R) | 625.00 kJ/ohms |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 25 kA |
Specific energy [L,N-PE] (W/R) | 156.25 kJ/ohms |
Nominal discharge current (8/20 µs) [L/N-PE]/[L+N-PE] (In ) | 25 / 50 kA |
Voltage protection level [L-PE]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 50 kArms |
Follow current limitation / Selectivity | no tripping of a 20 A gG fuse up to 50 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 315 A gG |
Max. backup fuse (L-L') | 125 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L, L', N, N', PE, 9) (min.) | 10 mm2 solid / flexible |
Cross-sectional area (L, N, PE) (max.) | 50 mm2 stranded / 35 mm2 flexible |
Cross-sectional area (L', N', 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94 V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 315 A gG |
Use for 16.7 Hz traction power supply systems | |
– Nominal voltage (a.c.) (UN ) | 230 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 125 A gG @ 16,7 Hz |
Le produit 951110 a été ajouté au bloc-notes
Le produit 951110 a été ajouté au panier.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) [L-N] (UC ) | 264 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) [N-PE] (UC (N-PE) ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) | 50 kA |
Specific energy [L+N-PE] (W/R) | 625.00 kJ/ohms |
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) | 25 / 50 kA |
Specific energy [L-N]/[N-PE] (W/R) | 156.25 / 625.00 kJ/ohms |
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In ) | 25 / 50 kA |
Voltage protection level [L-N]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability [L-N]/[N-PE] (Ifi ) | 50 kArms / 100 Arms |
Follow current limitation / Selectivity | no tripping of a 20 A gG fuse up to 50 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 315 A gG |
Max. backup fuse (L-L') | 125 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic | 1200 V / 200 ms – withstand |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L, L', N, N', PE, 9) (min.) | 10 mm2 solid / flexible |
Cross-sectional area (L, N, PE) (max.) | 50 mm2 stranded / 35 mm2 flexible |
Cross-sectional area (L', N', 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94-V-0 |
Place of installation | indoor installation |
Degree of protection | IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 315 A gG |
Supplementary data: | --------------------------------- |
– Voltage protection level [L-PE] (UP ) | 2.2 kV |
Use for 16.7 Hz traction power supply systems | |
– Nominal voltage (a.c.) (UN ) | 230 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 125 A gG @ 16,7 Hz |
Le produit 951115 a été ajouté au bloc-notes
Le produit 951115 a été ajouté au panier.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) [L-N] (UC ) | 264 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) [N-PE] (UC (N-PE) ) | 255 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L+N-PE] (Itotal ) | 50 kA |
Specific energy [L+N-PE] (W/R) | 625.00 kJ/ohms |
Lightning impulse current (10/350 µs) [L-N]/[N-PE] (Iimp ) | 25 / 50 kA |
Specific energy [L-N]/[N-PE] (W/R) | 156.25 / 625.00 kJ/ohms |
Nominal discharge current (8/20 µs) [L-N]/[N-PE] (In ) | 25 / 50 kA |
Voltage protection level [L-N]/[N-PE] (UP ) | ≤ 1.5 / ≤ 1.5 kV |
Follow current extinguishing capability [L-N]/[N-PE] (Ifi ) | 50 kArms / 100 Arms |
Follow current limitation / Selectivity | no tripping of a 20 A gG fuse up to 50 kArms (prosp.) |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 315 A gG |
Max. backup fuse (L-L') | 125 A gG |
Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 440 V / 120 min. – withstand |
Temporary overvoltage (TOV) [N-PE] (UT) – Characteristic | 1200 V / 200 ms – withstand |
Operating temperature range [parallel] / [series] (TU ) | -40 °C ... +80 °C / -40 °C ... +60 °C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area (L, L', N, N', PE, 9) (min.) | 10 mm2 solid / flexible |
Cross-sectional area (L, N, PE) (max.) | 50 mm2 stranded / 35 mm2 flexible |
Cross-sectional area (L', N', 9) (max.) | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Enclosure material | thermoplastic, red, UL 94-V-0 |
Place of installation / Degree of protection | indoors / IP 20 |
Capacity | 4 module(s), DIN 43880 |
Approvals | KEMA, VDE, UL |
Type of remote signalling contact | changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / flexible |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kArms (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
– Max. backup fuse (L) up to IK = 100 kArms | 315 A gG |
Supplementary data: | --------------------------------- |
– Voltage protection level [L-PE] (UP ) | 2.2 kV |
Use for 16.7 Hz traction power supply systems | |
– Nominal voltage (a.c.) (UN ) | 230 V |
– Nominal frequency (a.c.) (fN ) | 16.7 Hz |
– Max. backup fuse | 125 A gG @ 16,7 Hz |
Le produit 961305 a été ajouté au bloc-notes
Le produit 961305 a été ajouté au panier.
SPD as per EN 61673-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Energy coordination with terminal equipment (≤ 10 m) | Type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 264 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3-PEN] (Itotal ) | 75 kA |
Specific energy [L1+L2+L3-PEN] (W/R) | 1.40 MJ/ohms |
Lightning impulse current (10/350 µs) [L-PEN] (Iimp ) | 25 kA |
Specific energy [L-PEN] (W/R) | 156.25 kJ/ohms |
Nominal discharge current (8/20 µs) [L-PEN] (In ) | 25 kA |
Voltage protection level (UP ) | ≤ 1,5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 50 kArms |
Integrated overcurrent protection | Yes, ACI technology |
Short-circuit strength (ISCCR ) | 50 kArms |
Response time (tA ) | ≤ 100 ns |
Temporary overvoltage (TOV) (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range (TU ) | -40°C to +80°C |
Operating state / fault indication | Green / red (inspection window) |
Module disconnection indication | Green (side view) |
Number of ports | 1 |
Cross-sectional area (L1, L2, L3, PEN, 9) (min.) | 6 mm² solid / fine-stranded |
Cross-sectional area (L1, L2, L3, PEN, 9) (max.) | 35 mm² stranded / 25 mm² fine-stranded |
For mounting on | 35-mm DIN rail as per EN 60715 / busbar |
Place of installation | Indoor |
Degree of protection | IP 20 |
Capacity | 11 module(s), DIN 43880 |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kAeff (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
Le produit 961405 a été ajouté au bloc-notes
Le produit 961405 a été ajouté au panier.
SPD as per EN 61673-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
Energy coordination with terminal equipment (≤ 10 m) | Type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 230 / 400 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 264 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal ) | 100 kA |
Specific energy [L1+L2+L3+N-PE] (W/R) | 2.50 MJ/ohms |
Lightning impulse current (10/350 µs) [L, N-PE] (Iimp ) | 25 kA |
Specific energy [L,N-PE] (W/R) | 156.25 kJ/ohms |
Nominal discharge current (8/20 µs) [L/N-PE] (In ) | 25 kA |
Voltage protection level [L-PE]/[N-PE] (UP ) | ≤ 1,5 kV |
Open-circuit voltage of the combination wave generator (UOC ) | 20 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 50 kArms |
Integrated overcurrent protection | Yes, ACI technology |
Short-circuit strength [L-PE]/[N-PE] (ISCCR ) | 50 kAeff |
Response time (tA ) | ≤ 100 ns |
Temporary overvoltage (TOV) (UT) – Characteristic | 440 V / 120 min. – withstand |
Operating temperature range (TU ) | -40°C to +80°C |
Operating state / fault indication | Green / red (inspection window) |
Module disconnection indication | Green (side view) |
Number of ports | 1 |
Cross-sectional area (L1, L2, L3, N, PE, 9) (min.) | 6 mm² solid / fine-stranded |
Cross-sectional area (L1, L2, L3, N, PE, 9) (max.) | 35 mm² stranded / 25 mm² fine-stranded |
For mounting on | 35-mm DIN rail as per EN 60715 / busbar |
Place of installation | Indoor |
Degree of protection | IP 20 |
Capacity | 11 module(s), DIN 43880 |
Extended technical data: | Use in switchgear installations with prospective short-circuit currents of more than 50 kArms |
– Max. prospective short-circuit current | 100 kAeff (220 kApeak) |
– Limiting/cancelling of mains follow currents | up to 100 kArms (220 kApeak) |
Le produit 961151 a été ajouté au bloc-notes
Le produit 961151 a été ajouté au panier.
SPD according to EN 61643-11 / IEC 61643-11 | type 1 + type 2 / class I + class II |
Energy coordination with terminal equipment (≤ 10 m) | Type 1 + type 2 + type 3 |
Nominal voltage (a.c.) (UN ) | 800 V (50 / 60 Hz) |
Max. continuous operating voltage (a.c.) (UC ) | 880 V (50 / 60 Hz) |
Lightning impulse current (10/350 µs) [1,2-3] (Iimp ) | 12.5 kA |
Specific energy [1,2-3] (W/R) | 39.06 kJ/Ohm |
Nominal discharge current (8/20 µs) [1,2-3] (In ) | 20 kA |
Voltage protection level [1,2-3] (UP ) | ≤ 4 kV |
Follow current extinguishing capability (a.c.) (Ifi ) | 50 kArms |
Follow current limitation / Selectivity | No tripping of a 35 A gG fuse up to 50 kArms (prosp.) |
Short-circuit withstand capability [1,2-3] (ISCCR ) | 50 kArms |
Response time (tA ) | ≤ 100 ns |
Max. backup fuse (L) up to IK = 50 kArms | 160 A gG |
Operating temperature range (parallel connection) (TUP ) | -40°C to +80°C |
Operating state / fault indication | green / red |
Number of ports | 1 |
Cross-sectional area [1,2,3] (min.) | 6 mm2 solid / fine-stranded |
Cross-sectional area [1,2,3] (max.) | 35 mm2 stranded / 25 mm2 fine-stranded |
For mounting on | 35 mm DIN rails acc. to EN 60715 |
Place of installation | Indoor |
Degree of protection | IP 20 |
Capacity | 8 module(s), DIN 43880 |
Type of remote signalling contact | yes / changeover contact |
Switching capacity (a.c.) | 250 V / 0.5 A |
Switching capacity (d.c.) | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | max. 1.5 mm2 solid / fine-stranded |
Supplementary data: | --------------------------------- |
– Anti-PID voltage (U1-3 + UPID ) | 508 VAC + 750 VDC – withstand |